BMS

The Renbin BMS employs a three-tier BMS management architecture, enabling hierarchical data management and safety protection for modules, clusters, and battery stacks.

WhatsApp:

  • Product Description
  • Product Introduction

    The Renbin BMS employs a three-tier BMS management architecture, enabling hierarchical data management and safety protection for modules, clusters, and battery stacks.

    Three layers of independent hardware protection ensure that, in the event of a single-layer failure, system‑level protective actions can be triggered autonomously. Combined with the Karman filtering algorithm and Songdu Energy’s proprietary SOC estimation algorithm, this solution achieves an SOC accuracy within 5%. Furthermore, it introduces industry‑first leakage‑detection and internal‑resistance measurement capabilities, enabling cell‑level internal‑resistance assessment with a conformity rate of up to 95% compared to specialized equipment.

    Product Features

    ■ Tier-3 BMS Management Architecture

    ■ Layer 7 Software-Based Proactive Protection

    ■ Multi-level hard-wired independent protection

    ■ EMC Protection Level 4

    ■ Karman Filter SOC Algorithm

    ■ Complies with the IEC 61508 functional safety standard

    ■ 0.1-class accuracy in cell voltage measurement

    ■ Pioneered leakage and internal resistance detection functions

    Communication Topology

    Technical Specifications

    Product model SDBMS1000PSA
    Collection Parameters
    Battery-side voltage acquisition 0~1500V (±0.2%FS)
    Ground insulation resistance 0~65535 kΩ (±5%RD ±10 kΩ)
    SOC/SOE ≤8%
    Cumulative battery level ≤3%
    Number of single-cell voltage acquisition channels 18MAX (default 12)
    Single-cell voltage acquisition range 0~5V
    Single-cell voltage acquisition accuracy 1‰FS
    Total pressure acquisition range 16~90V/1‰FS
    Number of module temperature acquisition channels 8max
    Temperature acquisition range -40~125℃
    Temperature acquisition accuracy ±1℃FS
    Contact parameters
    Dry contact input 14 channels, 0~12V
    Dry contact output 30V/2A, 1 channel
    Wet node output 24V/2A, 5 channels
    PCS Hard Contact Maximum support: 30 VDC, 5 kHz
    Communication Parameters  
    External Communication Interface CAN2/ETH2/RS4853/RS2321
    Communication baud rate 250 kbps / 100 Mbps / 9600 bps / 19200 bps
    Communication protocol Default: Modbus-TCP/IEC61850 (MMS)
    Other parameters
    Operating temperature -20~65℃
    Operating humidity 5%~95% RH, no condensation
    Altitude 70 kPa~106 kPa
    Operating voltage range 18~30V/25W
    Balancing function Bidirectional Active Balancing / 5A max
    Certification Standards GB/T 34131

Keywords:

Get More Product Information for Free

* Note: Please fill in the information accurately and keep communication open. We will contact you as soon as possible.

Submit

Related Products


WTD-10/630A High Voltage Load Switch

WTD-10/630A High Voltage Load Switch

BHA-10/630A Export Type Isolating Switch

BHA-10/630A Export Type Isolating Switch

YB Prefabricated Substation

The B series prefabricated substation is used in 6KV and 10KV ring network power supply, dual power supply, or terminal power supply systems, serving as high-voltage distribution metering, compensation control, and protection device.

YB M/YB P Prefabricated Substation

The YBM and YBP series prefabricated substations are compact complete power distribution units that combine high-voltage electrical equipment, transformers, and low-voltage electrical equipment.