YB Prefabricated Substation
- Product Description
-
Product Overview
The YB series prefabricated substations are used for 6KV and 10KV ring network power supply, dual power supply, or terminal power supply systems, serving as high-voltage distribution metering, compensation control, and protection devices. Besides the transformer installed inside the prefabricated substation, the high-voltage side is equipped with four-position load switches, two-position load switches, backup protection fuses, and plug-in fuses; the low-voltage side is equipped with control electrical appliances and distribution electrical appliances according to user requirements, compensation devices, and electric energy meters. The ZGS series prefabricated substations can be used indoors or outdoors and are widely applied in industrial parks, residential communities, commercial centers, and high-rise buildings.
Model Meaning and Classification
YB
6
12/0.4
□
Prefabricated Substation
Design Serial Number
Rated Voltage (High Voltage/Low Voltage)
Transformer Capacity (KVA)
Normal Operating Conditions
1. Altitude ≤1000m (design separately if exceeding this range)
2. Wind Pressure: not greater than 70pa (equivalent to 35m/s)
3. Humidity: daily average not greater than 95%; monthly average not greater than 90%
4. Ambient Temperature: maximum temperature +40℃; minimum temperature -45℃
5. Seismic Level: horizontal acceleration 0.4m/s²; vertical acceleration 0.15m/s²
6. Earthquake Intensity: 8 degrees
7. Installation Site Inclination: not greater than 3°
8. Installation Environment: surrounding environment should not be subject to obvious pollution from corrosive, flammable gases, or water vapor; installation site should have no severe vibrationMain Technical Parameters
Item
Unit
Technical Parameters
Rated Voltage: Primary/Secondary
KV
10/0.4
Maximum Operating Voltage: Primary
KV
12
Rated Frequency
Hz
50
Rated Capacity
kVA
125, 225, 300, 500, 630, 800, 1000
Imin Power Frequency Withstand Voltage
KV
35
Lightning Impulse Withstand Voltage
KV
75
Short-time Withstand Current
KA
12kA/2s; 16kA/1s
High-voltage Backup Current-limiting Fuse Breaking Capacity
KA
50
No-load Tap Changer
10kV±2x2.5%
Ambient Temperature
℃
-45~40
Allowable Temperature Rise
℃
65